XMT *908 series intellective temperature control meter
Instruction manual
Ⅰ、Main technical specification
l Measurement deviation: ≤±0.5%F·S±1
l Cold end compensating deviation: ≤±2.0℃
l Sampling cycle: 0.5S
l Control cycle: relay output 2~120S , other is 2S.
l Relay output contact capacity: AC250V/7A (resistance load) or AC250V/0.3A (perceptual load)
l Driving controllable pulse output: ≥3V scope, ≥40us width’s over zero or trigger contact pulse
l Driving solid relay signal output: driving electric current≥15mA, voltage≥9V.
l Continuous PID : 0~10mA (load 500±200Ω), 4~20mA (load 250±100Ω),
or 0~5V (load≥100kΩ) , 1~5V (load≥100kΩ)
l Power supply: AC85V~242V, 50/60Hz
l Working condition: temperature 0~50.0℃, relative humidity≤85%RH, without corrode and strong electric radiation.
Ⅱ、Product code:
XMT □ 9 □ 8 &n…